TECHNICAL SPECIFICATIONS

THE STANDARD FEATURES OF CANADIAN POWER SOLUTIONS STABILIZERS

DESCRIPTIONS

STANDARD
SINGLE PHASE

STANDARD
THREE PHASE

HEAVY INDUSTRIAL
THREE PHASE

MODEL

CEM

CET

CET-Y

INPUT VOLTAGE

A, B, C, D and E refer to the next table

OUTPUT VOLTAGE

220/230V ac

380/415V ac

380/415V ac

RATED KVA

1KVA – 30 KVA

3KVA – 300 KVA

110KVA – 4000 KVA

OUTPUT WAVE FORM

SINE WAVE

RESPONSE TIME

0.02 – 0.04 SEC/V

0.02 – 0.04 SEC/V

0.02 – 0.06 SEC/V

OUTPUT ACCURACY

±1.5%

±1.5%

±1%

FREQUENCY

50Hz / 60Hz

EFFICIENCY

> 98%

OVER VOLTAGE PROTECTION TV SS (optional)

SURGE SUPPRESSOR

TEMPERATURE SENSOR

ON REQUEST

BY PASS LINE

ON REQUEST

SOFT START

ON REQUEST

OVER CURRENT PROTECTION

MCB/MCCB

MCB/MCCB

ON REQUEST

OPEN CIRCUIT PHASE SENSING

PHASE SENSING RELAY

ON REQUEST

ON REQUEST

AUTOMATIC OUTPUT DELAY SYSTEM

TIMER DELAY

ON REQUEST

ON REQUEST

OPERATING TEMPERATURE

-15 °C TO +45 °C


THE INPUT VOLTAGE RANGE IS SHOWN AS PERCENTAGE OF THE PRE-SET VOLTAGE

SERIES

INPUT VOLTAGE RANGE FOR
OUTPUT ACCURACY ±1.5%

INPUT VOLTAGE RANGE FOR
OUTPUT ACCURACY ±5%

A

±10%

-14%          +16%

B

±15%

-19%          +21%

C

±20%

-24%          +26%

D

±25%

-29%          +31%

E

±30%

-